Print Back

Thermoplastic PVC jacket with integral bonding wire 1/2" through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type CW. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 1/2" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 1/2" thru 3". Conduit shall be UL listed, CSA certified and IP 67 rated

more
Unidade de medida

Especificações

Tipo

CW

Tamanho comercial elétrica

1 in27 mm

Comprimento

400 ft121.92 m

Embalagens

Bobinas Pequenas

Diâmetro Interior

1.041 to 1.066 in26.441 to 27.076 mm

Diâmetro Externo

1.290 to 1.315 in32.766 to 33.401 mm

Aprox. Dentro Bend Radius

6.3 in160 mm

Aprox. Peso por 100 ft

71 lbs32.2 kg

Cor

Azul

Nota

Other colors available upon request.
3/8" & 4" trade sizes available on special order.

Certificações


UL Listed & CSA Certified

Cross-Reference #

231044 55-09-36-04 6404-41-00 CB CBLA-13 CBLT-1 ULBLUE

Core Material

Galvanized Steel

Ingress Protection (IP) Rating

Ingress Protection (IP) 66/67

Jacket Material

Polyvinyl Chloride (PVC)

Jacket Benefits

Liquid Tight Oil Resistant

Instalação

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 1/2" through 1-1/4, if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 1/2" through 3".
  • Approved for direct burial and in concrete trade sizes 1/2" through 3".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

Artigos de NEC

N/A

  • Article 250.118 (6) Equipment Grounding
  • Article 300.22 (D) Information Technology Equipment
  • Article 350 Liquid-Tight Flexible Metal Conduit (LFMC)
  • Article 501.10 (B) (2) Class I Div. 2
  • Article 502.10 (A) (2) and (B) (2) Class II Div. 1 & 2
  • Article 503.10 (A) (3) and (B) Class III Div. 1 & 2
  • Article 620.21 Elevator Wiring Methods
  • Article 645.5 (E) (2) Under Raised Floors

Aplicativo

N/A

Computer Wiring Meets Requirements of NEC
Temperature Range: -40°F to +176°F (-40°C to +80°C)