Thermoplastic PVC jacket with integral bonding wire 3/8" through 1-1/4"

Conduit shall be Anaconda SEALTITE® Type UA. Conduit shall provide a flexible liquid-tight raceway for wiring and shall be constructed of continuously interlocked hot dipped zinc galvanized steel core with an integral bonding wire in sizes 3/8" thru 1-1/4". Conduit shall have a sunlight resistant and flame retardant PVC jacket in electrical trade sizes 3/8" thru 4". Conduit shall be UL listed, CSA certified and IP 67 rated when installed with approved end connectors.

Especificações

Tipo

N/A UA

Embalagens

N/A Embalagem Padrão

Cor

N/A Cinza

Cores Opcionais

N/A Cinza

Certificações

N/A
UL Listed & CSA Certified

Cross-Reference #

N/A LA-12

Core Material

N/A Galvanized Steel

Ingress Protection (IP) Rating

N/A Ingress Protection (IP) 66/67

Jacket Material

N/A Polyvinyl Chloride (PVC)

Jacket Benefits

N/A Liquid Tight Oil Resistant

Instalação

N/A

  • Conduit used with standard liquid-tight connector for easy installation. IP 67 Rated when installed with approved connectors.
  • Approved for both exposed and concealed locations. Rated for temperature ranges -40ºF to + 176ºF (-40ºC to +80ºC).
  • Approved as an equipment grounding conductor in sizes 3/8" through 1-1/4" if the total grounding path is 6 ft. or less and the circuit conductors are protected by over 20 amps for 3/8" and 1/2" and 60 amps or less for 3/4" through 1-1/4".
  • Suitable for use in hazardous locations per NEC Articles 501 Class I Div. 2, Article 502 Class II Div. 1 & 2, Article 503 Class III Div. 1 & 2.
  • Manufactured in a full range of trade sizes from 3/8" through 4".
  • Approved for direct burial and in concrete trade sizes 3/8" through 4".
  • Complies with UL Standard 360 File No. E18917; CSA C22.2 File No. 158897; and NEC Article 350.

Artigos de NEC

N/A

  • Artigo 250.118 (6) Aterramento de Equipamentos
  • Artigo 300.22 (D) Equipamentos de Tecnologia da Informacao
  • Artigo 350 Eletroduto Metalico Flexivel Impermeavel (LFMC)
  • Artigo 501.10 (B) (2) Classe I Div. 2
  • Artigo 502.10 (A) (2) e (B) (2) Classe II Div. 1 e 2
  • Artigo 503.10 (A) (3) e (B) Classe III Div. 1 e 2
  • Artigo 620.21 Metodos de Fiacao de Elevadores
  • Artigo 645.5 (E) (2) Sob Pisos Elevados

Aplicativo

N/A Where UL Listing is Required and Conduit Grounding is Necessary
Temperature Range: -40ºF to +176ºF (-40ºC to +80ºC)